Thermocouple Extension wire Type EX-FEP/FEP-2×0.6
Description:

1. SUBJECT
This specification covers the requirements for FEP insulated, FEP sheathed
thermocouple extension cable, type EX, 2×1/0.6mm, stranded wire.

2. TECHNICAL FEATURES

 

 

A. Conductors:
Stranded thermocouple extension wire

 

       Conductors Size(AWG)        NO.of Strands &Gauge
       22        1/0.6mm

 

B. Insulation:
Extruded FEP ( 200℃)

       Nominal Insulation Thickness        0.21mm±0.2mm

 

Color code

       Positive        Color        Negative        Color
       Chromel        Purple        Alumel        Red

 

C. Assembly:
Two conductors (positive and negative) parallel construction.

D. Overall Jacket
Extruded FEP ( 200℃)

       Nominal Sheath Thickness        0.25mm±0.2
       Color code        Purple

 

3. DIMENSIONS AND TOLERANCES

 

       Dimensions/tolerances(mm)        1.65±0.25×2.50±0.25

 

4. CALIBRATION TOLERANCE

 

       Temperature range        Standard tolerance        Special tolerance
       0º to 200ºC        ±2.2℃ or 0.75%        ±1.1℃ or 0.4%

 

 